1. United States
  2. All 3M Products
  3. Electrical
  4. Power Cable Connectors
  5. Power Cable Terminations
  6. 3M™ Cold Shrink QT-II Outdoor Termination Kit 5642, JCN Shielding, 15 kV, 0.84-1.38 in (21-35 mm) Cable Insul. O.D., 1/kit

3M™ Cold Shrink QT-II Outdoor Termination Kit 5642, JCN Shielding, 15 kV, 0.84-1.38 in (21-35 mm) Cable Insul. O.D., 1/kit

  • Part Number 5642
  • 3M ID 7000057845
  • UPC 00054007119708
Voltage 15 kV
Conductor Sizes (Imperial) 3/0 AWG, 4/0 AWG, 250 kcmil, 300 kcmil, 350 kcmil
Insulation Outer Diameter (Metric) 21.336 mm, 21.59 mm, 21.844 mm, 22.098 mm, 22.352 mm, 22.606 mm, 22.86 mm, 23.114 mm, 23.368 mm, 23.622 mm, 23.876 mm, 24.13 mm, 24.384 mm, 24.638 mm, 24.892 mm, 25.146 mm, 25.4 mm, 25.654 mm, 25.908 mm, 26.162 mm, 26.416 mm, 26.67 mm, 26.924 mm, 27.178 mm, 27.432 mm, 27.686 mm, 27.94 mm, 28.194 mm, 28.448 mm, 28.702 mm, 28.956 mm, 29.21 mm, 29.464 mm, 29.718 mm, 29.972 mm, 30.226 mm, 30.48 mm, 30.734 mm, 30.988 mm, 31.242 mm, 31.496 mm, 31.75 mm, 32.004 mm, 32.258 mm, 32.512 mm, 32.766 mm, 33.02 mm, 33.274 mm, 33.528 mm, 33.782 mm
Insulation Outer Diameter (Imperial) 0.84 in, 0.85 in, 0.86 in, 0.87 in, 0.88 in, 0.89 in, 0.9 in, 0.91 in, 0.92 in, 0.93 in, 0.94 in, 0.95 in, 0.96 in, 0.97 in, 0.98 in, 0.99 in, 1 in, 1.01 in, 1.02 in, 1.03 in, 1.04 in, 1.05 in, 1.06 in, 1.07 in, 1.08 in, 1.09 in, 1.1 in, 1.11 in, 1.12 in, 1.13 in, 1.14 in, 1.15 in, 1.16 in, 1.17 in, 1.18 in, 1.19 in, 1.2 in, 1.21 in, 1.22 in, 1.23 in, 1.24 in, 1.25 in, 1.26 in, 1.27 in, 1.28 in, 1.29 in, 1.3 in, 1.31 in, 1.32 in, 1.33 in, 1.34 in, 1.35 in, 1.36 in, 1.37 in, 1.38 in
Cable Shielding Jacketed Concentric Neutral (JCN), Concentric Neutral (CN)
Number of Skirts 4

One-piece cold shrink termination.

High dielectric-constant material regulates the distribution of electric field stress

Suitable for outdoor, weather exposed applications

View more details

Details

Highlights
  • One-piece cold shrink termination
  • High dielectric-constant material regulates the distribution of electric field stress
  • Suitable for outdoor, weather exposed applications
  • Silicone rubber insulation is track-resistance and hydrophobic
  • Silicone cold shrink application provides constant radial pressure, "living seal"
  • Voltage ratings: 4 skirt kits up to 15kV, 110 kV BIL; 6 skirt kits up to 25/28 kV, 150 kV BIL; 8 skirt kits up to 35 kV, 200 kV BIL
  • Meets IEEE Standard 48, Class 1 for outdoor, weather-exposed applications

3M™ Cold Shrink QT II 5640 & 5650 Series Termination Kit includes a 4 skirt, 1 piece termination. It ensures a pliable, tight seal for jacketed concentric neutral power cables. The conjunction of high dielectric constant material and silicone rubber insulation allows the termination to withstand voltages up to 15kV.

3M™ Cold Shrink QT-II Silicone Rubber Termination Kits 5640 and 5650 are one-piece cold shrink terminations for jacketed concentric neutral (JCN) power cable. They meet the requirements of IEEE Standard 48, for Class 1 terminations.The 3M QT-II consists of a high dielectric constant (High-K) stress control tube insulated with a molded silicone skirted insulator. This four skirt design is rated 15 kV

Typical properties

Resources

Manufacturing Origin: USA

The designation that a product is Manufactured in the USA means the product undergoes substantial transformation in one of our U.S. Manufacturing plants. Some products contain imported components.

Note: 3M products offered on a government contract that require country of origin representation must be certified by 3M Trade Compliance. Contact customer service at 800-245-3573 to request a certificate.
For industrial/occupational use only. Not for consumer sale or use.

3M industrial and occupational products are intended, labeled, and packaged for sale to trained industrial and occupational customers for workplace use.  Unless specifically stated otherwise on the applicable product packaging or literature, these products are not intended, labeled, or packaged for sale to or use by consumers (e.g., for home, personal, primary or secondary school, recreational/sporting, or other uses not described in the applicable product packaging or literature), and must be selected and used in compliance with applicable health and safety regulations and standards (e.g., U.S. OSHA, ANSI), as well as all product literature, user instructions, warnings, and other limitations, and the user must take any action required under any recall, field action, or other product use notice.  Misuse of 3M industrial and occupational products may result in injury, sickness, death, or property damage.  For help with product selection and use, consult your on-site safety professional, industrial hygienist, or other subject matter expert.