26  Products
  • Specially designed for primary insulation of solid dielectric insulated wires and cable splicing rated to 1000 volts
  • Simple installation which requires no tools
  • Sealing of terminal lug barrels, conduit couplings and conduit-to-cable breakouts
  • Made of black EPDM rubber
 More...
View all details
For industrial/occupational use only. Not for consumer sale or use.
Overall Length (Imperial)
Overall_Length_Imperial
26 Products Available
Available options:
 Overall Length (Imperial)
All Options
Showing 24 of 26
Close
Specifications
Attribute Name
Value
Application
Insulation, mechanical protection, repair
Brand
3M™
Cable Shielding
Non-shielded, Tape Shield, UniShield®, Wire Shield
Cable Type
Non-Shieled, Solid Dielectric Power Cable, Power Cable
Case Quantity
10, 25, 50
Color Family
Black
Conductor Material
Aluminum, Copper
Conductor Size Range
10-1/0 AWG, 1250-2000 kcmil, 2-1/0 AWG, 2-4/0 AWG, 2/0 AWG-250 kcmil, 2/0 AWG–250 kcmil, 250-400 kcmil, 450-800 kcmil, 500-800 kcmil, 6-4 AWG, 900-1000 kcmil
Conductor Sizes
1 AWG, 1/0 AWG, 10 AWG, 1000 kcmil, 1250 kcmil, 1500 kcmil, 1750 kcmil, 2 AWG, 2/0 AWG, 2000 kcmil, 250 kcmil, 3/0 AWG, 300 kcmil, 350 kcmil, 4 AWG, 4/0 AWG, 400 kcmil, 500 kcmil, 6 AWG, 600 kcmil, 650 kcmil, 700 kcmil, 750 kcmil, 8 AWG, 800 kcmil, 900 kcmil, N/A
Connector Included
No
Dielectric Strength (V/mil)
365 V/mil
Elongation
750 %
Indoor/Outdoor
Both
Inner Diameter After Shrink (Imperial)
0.098 in, 0.189 in, 0.24 in, 0.398 in, 0.547 in, 0.661 in, 0.67 in, 0.839 in, 0.949 in, 1.268 in, 1.677 in
Inner Diameter After Shrink (Metric)
10.1 mm, 13.9 mm, 16.8 mm, 2.5 mm, 21.3 mm, 24.1 mm, 32.2 mm, 4.8 mm, 42.6 mm, 6.1 mm
Inner Diameter Before Shrink (Imperial)
0.669 in, 0.823 in, 0.941 in, 1.185 in, 1.38 in, 1.382 in, 1.937 in, 2.669 in, 2.85 in, 3.689 in
Inner Diameter Before Shrink (Metric)
17 mm, 20.9 mm, 23.9 mm, 30.1 mm, 35.1 mm, 49.2 mm, 67.8 mm, 72.4 mm, 93.7 mm
Manufacturing Origin
USA
Material
EPDM Rubber, EPDM-rubber
Maximum Connector Length
11.0 in, 12.0 in, 14.0 in, 2.0 in, 3.0 in, 5.0 in, 7.0 in, 8.0 in
Maximum Connector Length (Metric)
127.0 mm, 177.8 mm, 203.2 mm, 279.4 mm, 304.8 mm, 355.6 mm, 50.8 mm, 76.2 mm
Maximum Operating Temperature (Celsius)
90 Degree Celsius
Maximum Operating Temperature (Fahrenheit)
194 Degree Fahrenheit
Maximum Wire Gauge
20.9mm², 67.8mm², 93.7mm²
Minimum Operating Temperature (Fahrenheit)
-40 Degree Fahrenheit
Minimum Wire Gauge
10.1mm², 2.5mm², 32.2mm², 42.6mm²
Model
Cold-shrink
National Stock Number
5970015187748, 5975012342169
Number of Conductors
1
Operating Temperature (Celsius)
-40 up to +90°C
Overall Diameter (Metric)
20.9 mm, 23.9 mm, 67.8 mm, 93.7 mm
Overall Length (Imperial)
11 in, 12 in, 16 in, 18 in, 6 in, 8 in, 9 in
Overall Length (Metric)
152 mm, 152.4 mm, 203.2 mm, 228.6 mm, 279.4 mm, 304.8 mm, 381 mm, 406.4 mm, 457.2 mm
Product Color
Black
Product Type
Cold shrinking, Splice
Relaxed Tube Length
11 in, 12 in, 15 in, 16 in, 18 in, 6 in, 8 in, 9 in
Relaxed Tube Length (Metric)
152.4 mm, 203.2 mm, 228.6 mm, 279.4 mm, 304.8 mm, 381 mm, 406.4 mm, 457.2 mm
Shrink Ratio
2:1
Splice Type
Cold Shrink
Units per Case
10
Voltage
1 kV
Voltage Application
Low Voltage
Details
  • Specially designed for primary insulation of solid dielectric insulated wires and cable splicing rated to 1000 volts
  • Simple installation which requires no tools
  • Sealing of terminal lug barrels, conduit couplings and conduit-to-cable breakouts
  • Made of black EPDM rubber
  • Made of EPDM rubber which contains no chlorides or sulfur
  • Withstands temperatures of -40 to 194 degrees F (-40 to 90 degrees C)
  • Environmental sealing for communication and other non-electrical applications

3M™ Cold Shrink Connector Insulators 8420 and 8430 Series are designed using 3M’s proprietary cold shrink delivery system. Products are supplied prestretched on a removable core for efficiency and ease of installation. Removal of the core (unwinding) after positioning the splice allows the product to shrink into position forming a moisture-tight seal. The live memory action of the specially formulated EPDM material promotes a permanent, durable environmental seal and insulation, with a typical operating temperature range from -40–194°F (-40–90°C). The 8420 insulator meets requirements of ANSI C119-1 and Western Underground Guide 2.14 for secondary splices rated up to 1 kV. Applications: Primary electrical insulation for all solid dielectric (rubber and plastic) insulated wire and cable splicing rated to 1000 V. Good for repairs and environmental sealing for communication and other non-electrical applications. Important: Use insulation jacket or connector O.D. for final ordering criteria. * Mastic pads included for cable O.D. build-up. ** Kit contains adapters. *** These sizes are listed for availability only and are not designed to be used as primary insulation. These tubes are for conduit sealing and breakouts. ****Maximum connector length: 5.625” “Point of Purchase” packaging designated by “P”. Example: 8423-6P

For industrial/occupational use only. Not for consumer sale or use.

3M industrial and occupational products are intended, labeled, and packaged for sale to trained industrial and occupational customers for workplace use.  Unless specifically stated otherwise on the applicable product packaging or literature, these products are not intended, labeled, or packaged for sale to or use by consumers (e.g., for home, personal, primary or secondary school, recreational/sporting, or other uses not described in the applicable product packaging or literature), and must be selected and used in compliance with applicable health and safety regulations and standards (e.g., U.S. OSHA, ANSI), as well as all product literature, user instructions, warnings, and other limitations, and the user must take any action required under any recall, field action, or other product use notice.  Misuse of 3M industrial and occupational products may result in injury, sickness, death, or property damage.  For help with product selection and use, consult your on-site safety professional, industrial hygienist, or other subject matter expert.