Attribute Name
|
Value
|
---|---|
Application
|
Aerosol Formulations, Deposition Solvent, Heat Transfer, Immersion Cooling for Data Centers, Lubricant Deposition, Semiconductor Cooling, Test Equipment
|
Boiling Point (Celsius)
|
128 Degree Celsius
|
Boiling Point (Fahrenheit)
|
262 Degree Fahrenheit
|
Boiling Point Range
|
100 °C - 149 °C
|
Brand
|
Novec™
|
Cleaning Strength
|
Light Duty
|
Density
|
1.614 g/cm³
|
Dielectric Strength Range
|
>25 kV
|
Fluorocarbon Solubility
|
High
|
GWP (IPCC 2007)
|
100 (100 yr ITH)
|
GWP Range
|
Very Low
|
Hydrocarbon Solubility
|
Medium
|
Maximum Use Temperature (Celsius)
|
149 Degree Celsius
|
Maximum Use Temperature (Fahrenheit)
|
300.2 Degree Fahrenheit
|
Net Weight (Imperial)
|
12 lb, 40 lb, 600 lb
|
Net Weight (Metric)
|
18.14 kg, 272.15 kg, 5.44 kg
|
Overall Height (Imperial)
|
17 in, 35 in, 9.63 in
|
Overall Height (Metric)
|
24.46 cm, 43.18 cm, 88.9 cm
|
Overall Length (Imperial)
|
11.44 in, 23.5 in, 9.56 in
|
Overall Length (Metric)
|
24.29 cm, 29.06 cm, 59.69 cm
|
Overall Width (Imperial)
|
11.44 in, 23.5 in, 9.56 in
|
Overall Width (Metric)
|
242.824 mm, 290.576 mm, 596.9 mm
|
Plastic Elastomer Compatibility
|
Excellent
|
Pour Point (Celsius)
|
-100 Degree Celsius
|
Pour Point (Fahrenheit)
|
-148 Degree Fahrenheit
|
Product Series
|
Novec 7500
|
Purity Grade
|
Standard
|
Replacement For
|
PFCs
|
Size (Imperial)
|
11.44 in x 11.44 in, 23.5 in x 23.5 in, 9.56 in x 9.56 in
|
Size (Metric)
|
242.824 mm x 24.29 cm, 290.576 mm x 29.06 cm, 596.9 mm x 59.69 cm
|
TDS Required
|
Yes
|
Volume (Imperial)
|
1 gal, 3.25 gal, 55 gal
|
Volume (Metric)
|
12.3 L, 208.2 L, 3.79 L
|
3M™ Novec™ 7500 is a non-flammable fluid with a very low global warming potential (GWP.) Its' excellent inerting and dielectric properties make it a viable replacement for higher GWP fluids such as PFCs and PFPEs in a wide variety of applications.
3M™ Novec™ 7500 Engineered Fluid is useful as a heat transfer liquid for cooling reactors in the pharmaceutical and chemical processing industries. In the semiconductor industry, it is ideal for automated test equipment (ATE) and wafer processing equipment which requires extreme low temperatures. It has also been used as an autocascade refrigerant. 3M™ Novec™ 7500 Engineered Fluid has a very low Global Warming Potential (GWP) and offers reduced greenhouse gas emissions when compared to PFCs - without sacrificing performance.