| BACK TO START | BACK ONE STAGE | ||||||
| 33kV Indoor Single Core Polymeric Copper Wire Screened Cold Shrink Termination | |||||||
| Designed for, and approved by NPG/CE Electric | |||||||
| Kit Ref | Application Range Guide CSA (mm2) | Diameter over Primary Insulation (mm) | Accepted Lug Diameter (mm) | Termination Body | Approved Lug Included | ||
| 94-EP620-2-NY59 | 70 - 240 | 21.1 - 38.9 | 39 | QTIII | VETB21-12UTB | ||
| 94-EP630-2-NY60 | 300 - 400 | 26.7 - 45.7 | 45 | QTIII | VETB28-12UTB | ||
| 94-EP640-2-NY61 | 500 - 630 | 38.9 - 58.9 | 58 | QTIII | VETC33-12UTB | ||
| CLICK TO VIEW → | Installation Instruction | Type Test Report | |||||