BACK TO START BACK ONE STAGE
Indoor Three Core Polymeric Copper Wire / Copper Tape Screened, Armoured,  
and/or Lead Sheathed Cold Shrink Termination
Kit Ref Application Range Guide CSA (mm2) Diameter over Primary Insulation (mm) Accepted Lug Diameter (mm) Termination Body Lug Selector
Mechanical Compression
94-EB62-3 25 - 50 16.2 - 28.4 28 QTII tba tba
94-EB63-3 25 - 150 21.3 - 35.0 35 QTII click click
94-EB64-3 95 - 240 27.4 - 45.7 45 QTII click click
 
CLICK TO VIEW → Installation Instruction Type Test Report Technical Data Sheet
PLEASE NOTE: These QTII (6 Skirt) terminations are designed for 18/30kV Systems, and are tested to 170kV BIL only. They are not suitable for 19/33kV Systems