| BACK TO START | BACK ONE STAGE | |||||||
| 33kV Single Core Polymeric Copper Wire Screened Cold Shrink Joint | ||||||||
| Kit Ref | Application Range Guide CSA (mm2) | Diameter over Primary Insulation (mm) | Connector Dimensions | Earthing system | Splice Body | Outer Protection | Mechanical Connector Included | |
| Diameter (mm) | Length (mm) | |||||||
| 94-AP630-1/C | 120 - 240 | 28.4 - 42.0 | 23.3 - 42.0 | 170 | CFS/Stocking | QS2000 | Cold Shrink | 332-614-010 |
| 94-AP631-1/C | 185 - 400 | 28.4 - 42.0 | 23.3 - 42.0 | 170 | CFS/Stocking | QS2000 | Cold Shrink | 332-617-010 |
| CLICK TO VIEW → | Installation Instruction | Type Test Report | Technical Data Sheet | |||||
| 94-AC640-1/C | 300 - 630 | 31.5 - 52.6 | 22.1 - 52.6 | 210 | CFS/Stocking | QSIII | Cold Shrink | 332-598-015 |
| CLICK TO VIEW → | Installation Instruction | Type Test Report | Technical Data Sheet | |||||
| 94-AK620-1/C | 50 - 240 | 19.1 - 38.0 | 19.1 - 38.0 | 160 | CFS/Stocking | QS200 | Cold Shrink | 332-592-010 |
| 94-AK630-1/C | 300 - 630 | 35.9 - 66.0 | max 60 | 245 | CFS/Stocking | QS200 | Cold Shrink | 332-603-010 |
| CLICK TO VIEW → | Installation Instruction | Type Test Report | Technical Data Sheet | |||||
| When joining smaller cables, or those of dissimilar sizes, a build up kit may be required; | click to select | |||||||