| BACK TO START | BACK ONE STAGE | |||||
| 20kV Outdoor Three Core Polymeric Copper Wire / Copper Tape Screened, Armoured, | ||||||
| and/or Lead Sheathed Cold Shrink Termination | ||||||
| Kit Ref | Application Range Guide CSA (mm2) | Diameter over Primary Insulation (mm) | Accepted Lug Diameter (mm) | Termination Body | ||
| 94-EB61-3 | 25 - 35 | 16.2 - 24.4 | 24 | QTII | ||
| 94-EB62-3 | 50 - 120 | 16.2 - 28.4 | 28 | QTII | ||
| 94-EB63-3 | 120 - 240 | 21.3 - 35.0 | 35 | QTII | ||
| CLICK TO VIEW → | Installation Instruction | Type Test Report | Technical Data Sheet | |||