| BACK TO START | BACK ONE STAGE | ||||||
| 11kV Indoor Single Core Polymeric Copper Tape Screened, Armoured, Cold Shrink Termination | |||||||
| Kit Ref | Application Range Guide CSA (mm2) | Diameter over Primary Insulation (mm) | Accepted Lug Diameter (mm) | Termination Body | Armour Connection | ||
| 92-EP623-1 | 50 - 95 | 16.3 - 27.4 | 30 | QTIII | Brass support ring / Band It Strap * | * Recommended for use where Circulating Currents may be present | |
| 92-EP633-1 | 120 - 150 | 21.1 - 38.9 | 39 | QTIII | |||
| 92-EP643-1 | 185 - 400 | 21.1 - 38.9 | 39 | QTIII | |||
| 92-EP653-1 | 500 - 630 | 26.7 - 45.7 | 45 | QTIII | |||
| 92-EP629-1 | 50 - 95 | 16.3 - 27.4 | 30 | QTIII | Constant Force Spring ** | ** For applications where the armour will be glanded | |
| 92-EP639-1 | 120 - 300 | 21.1 - 38.9 | 39 | QTIII | |||
| 92-EP649-1 | 400 - 630 | 26.7 - 45.7 | 45 | QTIII | |||
| Can also be used for Copper Wire Screened Terminations, additional instruction is included | |||||||
| CLICK TO VIEW → | Installation Instruction | Installation Instruction | Type Test Report | Technical Data Sheet | |||
| Kit Ref | Application Range Guide CSA (mm2) | Diameter over Primary Insulation (mm) | Accepted Lug Diameter (mm) | Termination Body | |||
| 92-EB621-1-P | 50 - 150 | 15.9 - 30.0 | 30 | QTII | |||
| 92-EB631-1-P | 185 - 400 | 22.6 - 41.4 | 41 | QTII | |||
| 92-EB641-1-P | 300 - 630 | 27.3 - 49.3 | 49 | QTII | |||
| 92-EB651-1-P | 500 - 1000 | 31.5 - 51.5 | 51 | QTII | |||
| Can also be used for Copper Wire Screened Terminations, additional instruction is included | |||||||
| CLICK TO VIEW → | Installation Instruction | Type Test Report | Technical Data Sheet | ||||