BACK ONE STAGE
11kV Three Core Polymeric Copper Tape Screened, Armoured Cold Shrink Joint
Suitable for use as Transition to PILC/PICAS, or for Paper Cable Joint
Kit Ref Application Range Guide CSA (mm2) Diameter over Primary Insulation (mm) Connector Dimensions Earthing system Splice Body Mechanical Connector Included
Diameter (mm) Length (mm)
92-AV610-3/C 50 - 120 17.7 - 26.0 14.2 - 26.0 135 CFS/Stocking QS1000 332-607-010
92-AV620-3/C 150 - 240 22.3 - 33.2 18.0 - 33.2 145 CFS/Stocking QS1000 MF15/3M
92-AV630-3/C 240 - 400 28.4 - 42.0 23.3 - 42.0 220 CFS/Stocking QS1000 332-617-010
CLICK TO VIEW → Installation Instruction Type Test Report Technical Data Sheet
     
To select the Paper Cable Modules:
Kit Ref Transition Joint Paper Joint Screened Paper Module
92-AV610-3/C PILCL1 Qty 1 PILCL1 Qty 2 SPM2
92-AV620-3/C PILCL2 Qty 1 PILCL2 Qty 2 SPM2
92-AV630-3/C PILCL3 Qty 1 PILCL3 Qty 2 SPM2
CLICK TO VIEW → Installation Instruction (SPM2) Note: Installation instruction for the PILCL is included in the 92-AV Series
To select the outer Protection Kit:
Kit Ref Resin (Packs req'd) Mould Ref (Capacity)
92-AV610-3/C 1402FR  (2 x 7.18L) 1451PET (14 Litres)
92-AV620-3/C 1402FR  (2 x 7.18L) 1451PET (14 Litres)
92-AV630-3/C 1402FR  (3 x 7.18L) 1452PET (21 Litres)
*for standard buried applications it is also possible to use Prysmian 2 part polyurethane resin
CLICK TO VIEW → Technical Data Sheet for 1402FR Resin
Product Information for Moulds
When joining smaller cables, or those of dissimilar sizes, a build up kit may be required; click to select