BACK TO START BACK ONE STAGE
11kV Three Core Polymeric Copper Tape Screened, Armoured Cold Shrink Joint, and/or Lead Sheath
Kit Ref Application Range Guide CSA (mm2) Diameter over Primary Insulation (mm) Connector Dimensions Earthing system Splice Body Mechanical Connector Included
Diameter (mm) Length (mm)
92-AV610-3/C 50 - 120 17.7 - 26.0 14.2 - 28.0 135 CFS/Stocking QS1000 332-607-010
92-AV620-3/C 120 - 240 22.3 - 33.2 18.0 - 33.2 145 CFS/Stocking QS1000 MF15/3M
92-AV630-3/C 240 - 400 28.4 - 42.0 23.3 - 42.0 220 CFS/Stocking QS1000 332-617-010
CLICK TO VIEW → Installation Instruction Type Test Report Technical Data Sheet
     
To select the outer Mechanical Protection Kit:
Kit Ref Cold Shrink Application Resin Applicaton
Resin (Packs req'd) Mould Ref (Capacity)
92-AV610-3/C CS610-3 1402FR  (2 x 7.18L) 1451PET (14 Litres)
92-AV620-3/C CS620-3 1402FR  (2 x 7.18L) 1451PET (14 Litres)
92-AV630-3/C CS630-3 1402FR  (3 x 7.18L) 1452PET (21 Litres)
*for standard buried applications, Prysmian 2 part polyurethane resin is approved for use
CLICK TO VIEW → Technical Data Sheet for 1402FR Resin
Product Information for Moulds
When joining smaller cables, or those of dissimilar sizes, a build up kit may be required; click to select