| BACK TO START | BACK ONE STAGE | |||||||
| Polymeric Armoured Multi Core Low Voltage Joint for Flexible, Trailing, or Cable | ||||||||
| Tray Applications (not suitable for direct burial) | ||||||||
| Suitable for Polymeric Armoured Cables and/or Lead Sheath up to 1.9/3.3kV | ||||||||
| Suitable for Flame Resistant, Low Smoke, Zero Halogen Applications | ||||||||
| KIT REFERENCE | CROSS SECTIONAL AREA (mm˛) | CABLE OD RANGE (mm) | ARMOUR DIAMETER RANGE (mm) | CONNECTOR DIAMETER MAX (mm) | ||||
| Single Core 1kV |
Two Core 1kV | Three Core 1kV | Four Core 1kV | Three Core 3.3kV | ||||
| LC0-STFF48 | N/A | 1.5 - 4 | 1.5 - 2.5 | N/A | N/A | 10.0 - 17.0 | 4 - 15 | |
| LC1-STFF13 | N/A | 1.5 - 4 | 1.5 - 4 | 1.5 - 2.5 | N/A | 16.2 - 33.1 | 9 - 15 | 20 |
| LC2-STFF13 | 50 - 95 | 6 - 10 | 6 - 10 | 4 - 6 | N/A | 16.2 - 33.1 | 14 - 22 | 20 |
| LC3-STFF13 | 120 - 150 | 16 - 50 | 16 - 25 | 10 - 16 | N/A | 16.2 - 33.1 | 18.5 - 29 | 24 |
| LC4-STFF1 | 185 - 400 | 70 - 120 | 35 - 70 | 25 - 50 | 16 - 50 | 24.9 - 56.4 | 23.5 - 37 | 28 |
| LC5-STFF14 | 500 - 630 | 150 - 185 | 95 - 150 | 70 - 120 | 70 - 150 | 37.8 - 84.3 | 31 - 50 | 32 |
| LC6-STFF14 | 800 - 1000 | 240 - 300 | 185 - 240 | 150 - 185 | 185 - 240 | 37.8 - 84.3 | 44 - 70 | 45 |
| LC7-STFF15 | N/A | N/A | 300 | 240 - 300 | 300 | 62.5 - 128.5 | 44 - 70 | 45 |
| CLICK TO VIEW → | Installation Instruction | Type Test Report | Technical Data Sheet | ← LC JOINT | ||||
| CLICK TO VIEW → | Installation Instruction | Test data on request | Technical Data Sheet | ← STFF | ||||
| Please note: Fluted Connectors are not suitable for use with these joints. Connector used must have a smooth profile along the whole length. See above for maximum connector sizes. | ||||||||