BACK TO START BACK ONE STAGE  
Polymeric Armoured Multi Core Low Voltage Joint for Flexible, Trailing, or Cable
Tray Applications (not suitable for direct burial)
Suitable for Polymeric Armoured Cables and/or Lead Sheath up to 1.9/3.3kV
KIT REFERENCE CROSS SECTIONAL AREA (mm˛) CABLE OD RANGE (mm) ARMOUR DIAMETER RANGE (mm) CONNECTOR DIAMETER MAX (mm)
Single Core
1kV
Two Core 1kV Three Core 1kV Four Core 1kV Three Core 3.3kV
LC0 Tba Tba Tba Tba Tba 10.1 - 17.5 4 - 15 Tba
LC1 N/A 1.5 - 4 1.5 - 4 1.5 - 2.5 N/A 16.2 - 33.1 9 - 15 20
LC2 50 - 95 6 - 10 6 - 10 4 - 6 N/A 16.2 - 33.1 14 - 22 20
LC3 120 - 150 16 - 50 16 - 25 10 - 16 N/A 16.2 - 33.1 18.5 - 29 24
LC4 185 - 400 70 - 120 35 - 70 25 - 50 16 - 50 24.9 - 56.4 23.5 - 37 28
LC5 500 - 630 150 - 185 95 - 150 70 - 120 70 - 150 37.8 - 84.3 31 - 50 32
LC6 800 - 1000 240 - 300 185 - 240 150 - 185 185 - 240 37.8 - 84.3 44 - 70 45
LC7 N/A N/A 300 240 - 300 300 62.5 - 128.5 44 - 70 45
CLICK TO VIEW → Installation Instruction Type Test Report Technical Data Sheet
Please note: Fluted Connectors are not suitable for use with these joints. Connector used must have a smooth profile along the whole length. See above for maximum connector sizes.