- Provides a void-free seal to tape shield, wire shield and UniShield® power cables
- High dielectric-constant material regulates the distribution of electric field stress
- Suitable for outdoor applications
- Integrated design allows for easier installation, while sealing compounds provide constant radial pressure
More...
View all details
View Legal Disclaimer
For industrial/occupational use only. Not for consumer sale or use.
Attribute Name
|
Value
|
Brand
|
3M™
|
Breakout Boot
|
Yes
|
Cable Insulation Outside Diameter Range
|
0.70-0.92 in
|
Cable Insulation Outside Diameter Range (Metric)
|
17.8-23.4 mm
|
Cable Shielding
|
Tape Shield, UniShield®, Wire Shield
|
Case Quantity
|
1
|
Conductor Sizes (Imperial)
|
1 AWG, 1/0 AWG, 2 AWG, 2/0 AWG, 250 kcmil, 3/0 AWG, 300 kcmil, 350 kcmil, 4/0 AWG
|
Family
|
QT-III
|
Indoor/Outdoor
|
Outdoor Skirted
|
Insulation Level
|
100%, 133%
|
Insulation Outer Diameter (Imperial)
|
0.7 in, 0.71 in, 0.72 in, 0.73 in, 0.74 in, 0.75 in, 0.76 in, 0.77 in, 0.78 in, 0.79 in, 0.8 in, 0.81 in, 0.82 in, 0.83 in, 0.84 in, 0.85 in, 0.86 in, 0.87 in, 0.88 in, 0.89 in, 0.9 in, 0.91 in, 0.92 in
|
Insulation Outer Diameter (Metric)
|
17.78 mm, 18.034 mm, 18.288 mm, 18.542 mm, 18.796 mm, 19.05 mm, 19.304 mm, 19.558 mm, 19.812 mm, 20.066 mm, 20.32 mm, 20.574 mm, 20.828 mm, 21.082 mm, 21.336 mm, 21.59 mm, 21.844 mm, 22.098 mm, 22.352 mm, 22.606 mm, 22.86 mm, 23.114 mm, 23.368 mm
|
Insulation Rejacketing
|
Yes
|
Lug/Stem Connector Included in Kit
|
No
|
Manufacturing Origin
|
USA
|
Maximum Cable Outside Diameter
|
3.30 Inch
|
Maximum Cable Outside Diameter (Metric)
|
83.8 mm
|
Maximum Installed Length
|
9.80 in
|
Number of Conductors
|
3
|
Number of Skirts
|
2
|
Voltage
|
15 kV, 5 kV, 8 kV
|
Voltage Application
|
Medium Voltage
|
- Provides a void-free seal to tape shield, wire shield and UniShield® power cables
- High dielectric-constant material regulates the distribution of electric field stress
- Suitable for outdoor applications
- Integrated design allows for easier installation, while sealing compounds provide constant radial pressure
3M™ Cold Shrink QT III 7600 S 3G Series Termination Kit includes a skirted, 3 phase termination. It ensures a pliable, tight seal for tape shield, wire shield and UniShield® power cables. The conjunction of high dielectric constant material and sealing compounds allows the termination to withstand voltages of 5 to 35kV.
Legal Disclaimer
Manufacturing Origin: USA
The designation that a product is Manufactured in the USA means the product undergoes substantial transformation in one of our U.S. Manufacturing plants. Some products contain imported components.
Note: 3M products offered on a government contract that require country of origin representation must be certified by 3M Trade Compliance. Contact customer service at 800-245-3573 to request a certificate.
For industrial/occupational use only. Not for consumer sale or use.
3M industrial and occupational products are intended, labeled, and packaged for sale to trained industrial and occupational customers for workplace use. Unless specifically stated otherwise on the applicable product packaging or literature, these products are not intended, labeled, or packaged for sale to or use by consumers (e.g., for home, personal, primary or secondary school, recreational/sporting, or other uses not described in the applicable product packaging or literature), and must be selected and used in compliance with applicable health and safety regulations and standards (e.g., U.S. OSHA, ANSI), as well as all product literature, user instructions, warnings, and other limitations, and the user must take any action required under any recall, field action, or other product use notice. Misuse of 3M industrial and occupational products may result in injury, sickness, death, or property damage. For help with product selection and use, consult your on-site safety professional, industrial hygienist, or other subject matter expert.