Attribute Name
|
Value
|
---|---|
Application
|
Insulation, mechanical protection, repair
|
Brand
|
3M™
|
Cable Shielding
|
Tape Shield, UniShield®, Wire Shield
|
Cable Type
|
Cable with plastic and rubber insulation
|
Color Family
|
Gray
|
Conductor Material
|
Aluminum, Copper
|
Conductor Sizes (Imperial)
|
1/0 AWG, 2/0 AWG, 3/0 AWG
|
Conductor Sizes (Metric)
|
95 mm²
|
Division
|
ElectricalMarketsDivision
|
Halogen Free
|
No
|
Inner Diameter After Shrink (Imperial)
|
0.488 in
|
Inner Diameter After Shrink (Metric)
|
12.4 mm
|
Inner Diameter Before Shrink (Imperial)
|
0.949 in
|
Inner Diameter Before Shrink (Metric)
|
24.1 mm
|
Material
|
Silicone
|
Maximum Conductor Size (Imperial)
|
157 kcmil
|
Maximum Conductor Size (Metric)
|
95 mm²
|
Maximum Operating Temperature (Celsius)
|
260 Degree Celsius
|
Maximum Operating Temperature (Fahrenheit)
|
500 Degree Fahrenheit
|
Minimum Conductor Size (Imperial)
|
118 kcmil
|
Minimum Conductor Size (Metric)
|
50 mm²
|
Minimum Operating Temperature (Celsius)
|
-55 Degree Celsius
|
Minimum Operating Temperature (Fahrenheit)
|
-67 Degree Fahrenheit
|
Model
|
Cold-shrink
|
Number of Conductors
|
1
|
Operating Temperature (Celsius)
|
-55 up to +260°C
|
Overall Diameter (Metric)
|
24.1 mm
|
Overall Length (Imperial)
|
8 in
|
Overall Length (Metric)
|
203.2 mm
|
PlantAnalystID
|
ABBA-Z1GUQ
|
Product Color
|
Gray
|
Product Type
|
Cold Shrink
|
Relaxed Tube Length
|
8 in
|
Relaxed Tube Length (Metric)
|
203.2 mm
|
RoHS 2011/65/EU Compliant
|
Yes
|
RoHS EU Comments
|
RoHS 2011/65/EU compliant without exemption
|
Shrink Ratio
|
2:1
|
Splice Type
|
Cold Shrink
|
TDS Required
|
Yes
|
Voltage
|
1 kV
|
Voltage Application
|
Low Voltage
|
3M™ 8440 Series Cold Shrink Silicone Insulator is an insulating sleeve that is specially formulated from high temperature silicone rubber for moisture protection. It maintains resiliency and pressure, even after years of aging and exposure. This insulator ensures top moisture sealing for medium voltage, air insulated connectors and lugs. It offers resistance against acids, alkalis, fluid splashes, ozone, ultraviolet light and fire. This insulator is ideal for use in sheath repairs and electrical aircraft cables and it provides insulation for inline conductor transition connectors. RoHS 2011/65/EU Compliant.