  • 3M™ Cold Shrink QT-III Termination Kit 7600-T-3G Series for 5-35 kV
  • 3M™ Cold Shrink QT-III Termination Kit 7600-T-3G Series for 5-35 kV

    • Provides a void-free seal to tape shield, wire shield and UniShield® power cables
    • High dielectric-constant material regulates the distribution of electric field stress
    • Suitable for indoor applications
    • Silicone rubber insulation offers durability and reduces leakage currents in damp conditions
     More...
    All Options
    Close
    Specifications
    Attribute Name
    Value
    Agency Approvals
    IEEE
    Application
    Cable Connection, Cable Termination
    Brand
    3M™
    Breakout Boot
    Yes
    Cable Insulation Outside Diameter Range
    0.33-0.50 in, 0.50-0.70 in, 0.70-0.92 in, 0.92-1.18 in, 1.18-1.52 in
    Cable Insulation Outside Diameter Range (Metric)
    12.7-17.8 mm, 17.8-23.4 mm, 23.4-30.0 mm, 30.0-38.6 mm, 8.4-12.7 mm
    Cable Shielding
    Tape Shield, UniShield®, Wire Shield, Wire-Over-Tape Shield
    Case Quantity
    1
    Conductor Material
    Aluminum, Copper
    Conductor Size by Voltage
    (15 kV, 100%) 250-350 kcmil, (15 kV, 100%) 500-750 kcmil, (15 kV, 133%) 4/0 AWG-350 kcmil, (15 kV, 133%) 500-750 kcmil, (25/28 kV, 100%) 2/0 AWG-250 kcmil, (25/28 kV, 100%) 350-500 kcmil, (25/28 kV, 133%) 1-4/0 AWG, (25/28 kV, 133%) 250-500 kcmil, (35 kV, 100%) 1/0-3/0 AWG, (35 kV, 100%) 4/0 AWG-500 kcmil, (35 kV, 133%) 1/0 AWG-350 kcmil, (5 kV, 100%) 1-3/0 AWG, (5 kV, 133%) 2-2/0 AWG, (8 kV, 100%) 2-2/0 AWG, (8 kV, 133%) 2-2/0 AWG, (15 kV, 100%) 2-1 AWG, (5 kV, 100%) 1-3/0 AWG, (5 kV, 133%) 2-2/0 AWG, (8 kV, 100%) 2-2/0 AWG, 8 kV, 133%) 2-2/0 AWG, (5 kV, 100%) 4/0 AWG-350 kcmil, (5 kV, 133%) 3/0 AWG-350 kcmil, (8 kV, 100%) 3/0 AWG-350 kcmil, (8 kV, 133%) 3/0 AWG-350 kcmil, (15 kV, 100%) 1/0-4/0 AWG, (15 kV, 133%) 2 AWG-3/0 AWG, (5 kV, 100%) 4/0 AWG-350 kcmil, (5 kV, 133%) 3/0 AWG-350 kcmil, (8 kV, 100%) 3/0 AWG-350 kcmil, (8 kV, 133%) 3/0 AWG-350 kcmil, (15 kV, 100%) 1/0-4/0 AWG, (15 kV, 133%) 2-3/0 AWG, (25/28 kV, 100%) 1-1/0 AWG, (5 kV, 100%) 4/0 AWG-350 kcmil, (5 kV, 133%) 3/0 AWG-350 kcmil, (8 kV, 100%) 3/0 AWG-350 kcmil, 8 kV, 133%) 3/0 AWG-350 kcmil, (5 kV, 100%) 400-500 kcmil, (5 kV, 100%) 400-500 kcmil, (5 kV, 133%) 400-500 kcmil, (8 kV, 100%) 400-500 kcmil, (8 kV, 133%) 400-500 kcmil, (15 kV, 100%) 250-350 kcmil, (15 kV, 133%) 4/0 AWG-350 kcmil, (5 kV, 100%) 400-500 kcmil, (5 kV, 133%) 400-500 kcmil, (8 kV, 100%) 400-500 kcmil, 8 kV, 133%) 400-500 kcmil, (5 kV, 100%) 700-1000 kcmil, (5 kV, 100%) 700-1000 kcmil, (5 kV, 133%) 700-1000 kcmil, (8 kV, 100%) 700-1000 kcmil, (8 kV, 133%) 700-1000 kcmil, (15 kV, 100%) 500-750 kcmil, (15 kV, 133%) 500-750 kcmil, (5 kV, 100%) 700-1000 kcmil, (5 kV, 133%) 700-1000 kcmil, (8 kV, 100%) 700-1000 kcmil, 8 kV, 133%) 700-1000 kcmil, (5 kV, 100%) 8-2 AWG, (5 kV, 133%) 6-4 AWG, (8 kV, 100%) 6-4 AWG, (8 kV, 133%) 6-4 AWG, (5 kV, 133%) 400-500 kcmil, (5 kV, 133%) 700-1000 kcmil, (8 kV, 100%) 400-500 kcmil, (8 kV, 100%) 700-1000 kcmil, (8 kV, 133%) 400-500 kcmil, (8 kV, 133%) 700-1000 kcmil
    Conductor Sizes
    1 AWG, 1/0 AWG, 1000 kcmil, 2 AWG, 2/0 AWG, 250 kcmil, 3/0 AWG, 300 kcmil, 350 kcmil, 4 AWG, 4/0 AWG, 400 kcmil, 500 kcmil, 6 AWG, 600 kcmil, 700 kcmil, 750 kcmil, 8 AWG, 800 kcmil, 900 kcmil
    Connector Included
    None
    Family
    QT-III
    Indoor/Outdoor
    Indoor Non-skirted
    Insulation Level
    100%, 133%
    Insulation Outer Diameter (Imperial)
    0.33 in, 0.34 in, 0.35 in, 0.36 in, 0.37 in, 0.38 in, 0.39 in, 0.4 in, 0.41 in, 0.42 in, 0.43 in, 0.44 in, 0.45 in, 0.46 in, 0.47 in, 0.48 in, 0.49 in, 0.5 in, 0.51 in, 0.52 in, 0.53 in, 0.54 in, 0.55 in, 0.56 in, 0.57 in, 0.58 in, 0.59 in, 0.6 in, 0.61 in, 0.62 in, 0.63 in, 0.64 in, 0.65 in, 0.66 in, 0.67 in, 0.68 in, 0.69 in, 0.7 in, 0.71 in, 0.72 in, 0.73 in, 0.74 in, 0.75 in, 0.76 in, 0.77 in, 0.78 in, 0.79 in, 0.8 in, 0.81 in, 0.82 in, 0.83 in, 0.84 in, 0.85 in, 0.86 in, 0.87 in, 0.88 in, 0.89 in, 0.9 in, 0.91 in, 0.92 in, 0.93 in, 0.94 in, 0.95 in, 0.96 in, 0.97 in, 0.98 in, 0.99 in, 1 in, 1.01 in, 1.02 in, 1.03 in, 1.04 in, 1.05 in, 1.06 in, 1.07 in, 1.08 in, 1.09 in, 1.1 in, 1.11 in, 1.12 in, 1.13 in, 1.14 in, 1.15 in, 1.16 in, 1.17 in, 1.18 in, 1.19 in, 1.2 in, 1.21 in, 1.22 in, 1.23 in, 1.24 in, 1.25 in, 1.26 in, 1.27 in, 1.28 in, 1.29 in, 1.3 in, 1.31 in, 1.32 in, 1.33 in, 1.34 in, 1.35 in, 1.36 in, 1.37 in, 1.38 in, 1.39 in, 1.4 in, 1.41 in, 1.42 in, 1.43 in, 1.44 in, 1.45 in, 1.46 in, 1.47 in, 1.48 in, 1.49 in, 1.5 in, 1.51 in, 1.52 in
    Insulation Outer Diameter (Metric)
    10.16 mm, 10.414 mm, 10.668 mm, 10.922 mm, 11.176 mm, 11.43 mm, 11.684 mm, 11.938 mm, 12.192 mm, 12.446 mm, 12.7 mm, 12.954 mm, 13.208 mm, 13.462 mm, 13.716 mm, 13.97 mm, 14.224 mm, 14.478 mm, 14.732 mm, 14.986 mm, 15.24 mm, 15.494 mm, 15.748 mm, 16.002 mm, 16.256 mm, 16.51 mm, 16.764 mm, 17.018 mm, 17.272 mm, 17.526 mm, 17.78 mm, 18.034 mm, 18.288 mm, 18.542 mm, 18.796 mm, 19.05 mm, 19.304 mm, 19.558 mm, 19.812 mm, 20.066 mm, 20.32 mm, 20.574 mm, 20.828 mm, 21.082 mm, 21.336 mm, 21.59 mm, 21.844 mm, 22.098 mm, 22.352 mm, 22.606 mm, 22.86 mm, 23.114 mm, 23.368 mm, 23.622 mm, 23.876 mm, 24.13 mm, 24.384 mm, 24.638 mm, 24.892 mm, 25.146 mm, 25.4 mm, 25.654 mm, 25.908 mm, 26.162 mm, 26.416 mm, 26.67 mm, 26.924 mm, 27.178 mm, 27.432 mm, 27.686 mm, 27.94 mm, 28.194 mm, 28.448 mm, 28.702 mm, 28.956 mm, 29.21 mm, 29.464 mm, 29.718 mm, 29.972 mm, 30.226 mm, 30.48 mm, 30.734 mm, 30.988 mm, 31.242 mm, 31.496 mm, 31.75 mm, 32.004 mm, 32.258 mm, 32.512 mm, 32.766 mm, 33.02 mm, 33.274 mm, 33.528 mm, 33.782 mm, 34.036 mm, 34.29 mm, 34.544 mm, 34.798 mm, 35.052 mm, 35.306 mm, 35.56 mm, 35.814 mm, 36.068 mm, 36.322 mm, 36.576 mm, 36.83 mm, 37.084 mm, 37.338 mm, 37.592 mm, 37.846 mm, 38.1 mm, 38.354 mm, 38.608 mm, 8.382 mm, 8.636 mm, 8.89 mm, 9.144 mm, 9.398 mm, 9.652 mm, 9.906 mm
    Insulation Outside Diameter Range
    1.08 - 1.70 Inch
    Insulation Outside Diameter Range (Metric)
    27.4 - 43.2 mm
    Insulation Rejacketing
    Yes
    Lug/Stem Connector Included in Kit
    No
    Manufacturing Origin
    USA
    Material
    Silicone Rubber
    Maximum Cable Outside Diameter
    2.20 in, 2.80 in, 3.30 in, 3.90 in, 4.50 in
    Maximum Cable Outside Diameter (Metric)
    114.3 mm, 55.9 mm, 71.1 mm, 83.8 mm, 99.1 mm
    Maximum Installed Length
    12.00 in, 16.00 in, 8.50 in
    Maximum Wire Gauge
    500mm²
    Minimum Wire Gauge
    240mm²
    Number of Conductors
    3
    Product Color
    Gray
    Product Type
    Splice
    Splice Type
    Inline
    Typical Splice Length
    32 in
    Typical Splice Length (Metric)
    813 mm
    Voltage
    15 kV, 25 kV, 35 kV, 5 kV, 8 kV
    Voltage Application
    Medium Voltage
    Details
    • Provides a void-free seal to tape shield, wire shield and UniShield® power cables
    • High dielectric-constant material regulates the distribution of electric field stress
    • Suitable for indoor applications
    • Silicone rubber insulation offers durability and reduces leakage currents in damp conditions

    3M™ Cold Shrink QT III 7600 T 3G Series Termination Kit includes a non skirted, 3 phase termination. It ensures a pliable, tight seal for tape shield, wire shield and UniShield® power cables. The silicone rubber sealing compounds allow the termination to withstand voltages of 5 to 35kV.