  • 3M™ Cold Shrink QT-II Outdoor Termination Kit 4604, Tape/Wire/LC Shielding, 46 kV
  • 3M™ Cold Shrink QT-II Outdoor Termination Kit 4604, Tape/Wire/LC Shielding, 46 kV

    Part Number 46043M ID 80610731467UPC 00054007501923
    • For tape shield, wire shield and longitudinally corrugated power cables
    • High dielectric-constant material regulates the distribution of electric field stress
    • Suitable for outdoor, weather exposed applications
    • Silicone rubber insulation is track-resistance and hydrophobic
     More...
    View Legal Disclaimer
    Specifications
    Attribute Name
    Value
    Agency Approvals
    IEEE
    Arcing Distance
    30 in
    Arcing Distance (Metric)
    76.2 cm
    BIL
    250 kV
    Brand
    3M™
    Breakout Boot
    No
    Cable Insulation Outside Diameter Range
    1.31-2.10 in
    Cable Insulation Outside Diameter Range (Metric)
    33.2-53.4 mm
    Cable Shielding
    Longitudinally Corrugated (LC), Tape Shield, Wire Shield
    Case Quantity
    1
    Conductor Size Range
    4/0 AWG-600 kcmil
    Conductor Sizes
    250 kcmil, 300 kcmil, 350 kcmil, 4/0 AWG, 400 kcmil, 500 kcmil, 600 kcmil
    Creepage Distance
    46 in
    Creepage Distance (Metric)
    1.17 m
    Family
    QT-II
    Indoor/Outdoor
    Outdoor Skirted
    Insulation Level
    100%, 133%
    Insulation Outer Diameter (Imperial)
    1.31 in, 1.32 in, 1.33 in, 1.34 in, 1.35 in, 1.36 in, 1.37 in, 1.38 in, 1.39 in, 1.4 in, 1.41 in, 1.42 in, 1.43 in, 1.44 in, 1.45 in, 1.46 in, 1.47 in, 1.48 in, 1.49 in, 1.5 in, 1.51 in, 1.52 in, 1.53 in, 1.54 in, 1.55 in, 1.56 in, 1.57 in, 1.58 in, 1.59 in, 1.6 in, 1.61 in, 1.62 in, 1.63 in, 1.64 in, 1.65 in, 1.66 in, 1.67 in, 1.68 in, 1.69 in, 1.7 in, 1.71 in, 1.72 in, 1.73 in, 1.74 in, 1.75 in, 1.76 in, 1.77 in, 1.78 in, 1.79 in, 1.8 in, 1.81 in, 1.82 in, 1.83 in, 1.84 in, 1.85 in, 1.86 in, 1.87 in, 1.88 in, 1.89 in, 1.9 in, 1.91 in, 1.92 in, 1.93 in, 1.94 in, 1.95 in, 1.96 in, 1.97 in, 1.98 in, 1.99 in, 2 in, 2.01 in, 2.02 in, 2.03 in, 2.04 in, 2.05 in, 2.06 in, 2.07 in, 2.08 in, 2.09 in, 2.1 in
    Insulation Outer Diameter (Metric)
    33.274 mm, 33.528 mm, 33.782 mm, 34.036 mm, 34.29 mm, 34.544 mm, 34.798 mm, 35.052 mm, 35.306 mm, 35.56 mm, 35.814 mm, 36.068 mm, 36.322 mm, 36.576 mm, 36.83 mm, 37.084 mm, 37.338 mm, 37.592 mm, 37.846 mm, 38.1 mm, 38.354 mm, 38.608 mm, 38.862 mm, 39.116 mm, 39.37 mm, 39.624 mm, 39.878 mm, 40.132 mm, 40.386 mm, 40.64 mm, 40.894 mm, 41.148 mm, 41.402 mm, 41.656 mm, 41.91 mm, 42.164 mm, 42.418 mm, 42.672 mm, 42.926 mm, 43.18 mm, 43.434 mm, 43.688 mm, 43.942 mm, 44.196 mm, 44.45 mm, 44.704 mm, 44.958 mm, 45.212 mm, 45.466 mm, 45.72 mm, 45.974 mm, 46.228 mm, 46.482 mm, 46.736 mm, 46.99 mm, 47.244 mm, 47.498 mm, 47.752 mm, 48.006 mm, 48.26 mm, 48.514 mm, 48.768 mm, 49.022 mm, 49.276 mm, 49.53 mm, 49.784 mm, 50.038 mm, 50.292 mm, 50.546 mm, 50.8 mm, 51.054 mm, 51.308 mm, 51.562 mm, 51.816 mm, 52.07 mm, 52.324 mm, 52.578 mm, 52.832 mm, 53.086 mm, 53.34 mm
    Insulation Rejacketing
    No
    Maximum Installed Length
    28.0 in
    Number of Conductors
    1
    Number of Skirts
    12
    Product Series
    4600
    RoHS 2011/65/EU Compliant
    Undetermined
    RoHS EU Comments
    Contact 3M for information
    *Important RoHS information
    Voltage
    46 kV
    Details
    • For tape shield, wire shield and longitudinally corrugated power cables
    • High dielectric-constant material regulates the distribution of electric field stress
    • Suitable for outdoor, weather exposed applications
    • Silicone rubber insulation is track-resistance and hydrophobic
    • Silicone cold shrink application provides constant radial pressure, "living seal"
    • Withstands voltages up to 46kV and is 250kV BIL-rated
    • Meets IEEE Standard 48, Class 1 for outdoor, weather-exposed applications

    3M™ Cold Shrink QT II 4604 & 4605 Series Termination Kit includes a 12 skirt, 3 piece termination. It ensures a pliable, tight seal for tape shield, wire shield and longitudinally corrugated power cables. The conjunction of high dielectric constant material and silicone rubber insulation allows the termination to withstand voltages up to 46kV.

    3M™ Cold Shrink QT II 4604 & 4605 Series Termination Kit is designed for terminating medium voltage cables in outdoor applications. The track resistant, silicone rubber insulated termination has a hydrophobic property and offers a long lasting service life while minimizing leakage currents in wet conditions. The lower surface stress, high dielectric constant material offers an optimized BIL performance while ensuring a leak proof, compact fit. IEEE Standard 48 Approved for Class 1 terminations.

    Legal Disclaimer

    Manufacturing Origin: USA

    The designation that a product is Manufactured in the USA means the product undergoes substantial transformation in one of our U.S. Manufacturing plants. Some products contain imported components.

    Note: 3M products offered on a government contract that require country of origin representation must be certified by 3M Trade Compliance. Contact customer service at 800-245-3573 to request a certificate.
    Follow Us
    The brands listed above are trademarks of 3M.
    Change Location
    United States - English