combinations (line sets)

  • Great application when there is limited access due to the fan coil unit in position
  • System Highlights:
  • 2 Hour F Rating
  • 15 Minute T Rating on C-AJ-8217
  • 2-1/2” thick concrete floor
  • Double line set system - (1) nom. 1 in. diameter copper tube with ½ in. thick AB/PVC insulation, (3) nom 1 in. diameter non-insulated Type L copper tubes, (1) nom 1 in. diameter schedule 40 PVC drain pipe (open) and (4) 4-pair No. 18 AWG thermostat cables
  • Maximum 6” diameter opening
  • Annular space - point contact to 3-1/4”
  • 3M FIP 1-Step Foam installed to full depth of assembly
Concrete Floor or
Wall C-AJ-8217